Cylinder safety inspection — a pre-use checklist

Two minutes with every cylinder before you connect it. Habit, not bureaucracy.
Every full cylinder we deliver has been filled and checked at the depot. That doesn’t replace your own pre-use inspection — the cylinder may have travelled 200km or been bumped on a loading dock. A 2-minute check every time you connect saves lives.

The pre-use checklist

Run this check every time you put a fresh cylinder into service.

  1. Label present and legible. Gas name, grade, batch number, supplier. If it’s not labelled, don’t use it — period.
  2. Test date visible and in date. Stamped on the shoulder. Most industrial cylinders are on a 10-year interval. See next section for details.
  3. Valve cap fitted before connection. If missing, inspect the valve carefully.
  4. Valve threads clean. No debris, no tape residue, no oil or grease.
  5. No visible damage. Dents larger than 10mm, deep scores, bulges, or corrosion patches — reject the cylinder.
  6. Cylinder upright. If found laid down, stand it up and wait at least 30 minutes before use (especially acetylene).
  7. Valve turns freely. Open slightly to ensure no seized valve. Crack and close before connecting regulator.
  8. Connection fittings match. Don’t force a regulator onto the wrong thread.

Two minutes. Every time.

Understanding the test date stamp

Australian gas cylinders are requalified at intervals set by AS 2030. The test date is stamped near the neck in format like 03/22 (March 2022) or 03 22. After the interval expires, the cylinder must be hydrostatically tested before refill.

Cylinder typeTypical test interval
Steel high-pressure (O₂, N₂, Ar, He, CO₂)10 years
Acetylene (steel with porous mass)10 years
LPG (steel low-pressure)10 years
Composite-wrapped (lightweight)5 years (typical)

If the test date is within a year of expiring and the cylinder is on long-term hire, note it — the depot should be scheduling requalification. We handle this for hire cylinders; owned cylinders are your responsibility.

Signs to reject a cylinder

Don’t connect a cylinder if any of these are present:

  • Missing or illegible label.
  • Expired test date (past requalification window).
  • Visible dents larger than 10mm or deep scores anywhere.
  • Fire damage — scorch marks, paint blistering, or visible heat affect.
  • Bulges or distortion — catastrophic failure risk.
  • Valve damage — bent, cracked, or leaking.
  • Significant corrosion — surface rust is OK; deep pitting or loss of wall thickness is not.
  • Visible contamination on valve threads — oil, water, chemicals.

Any of these — return the cylinder to the depot marked for rejection. Don’t attempt to patch, repair, or use.

Checking for valve leaks

After you connect the regulator, always leak-check:

  1. Close the regulator outlet valve (if fitted) or make sure any downstream equipment is shut.
  2. Open the cylinder valve slowly.
  3. Apply a soapy-water solution (commercial leak-detect spray is ideal) around:
    • Cylinder valve stem seal
    • Valve-to-regulator connection
    • Regulator gauges
    • Any downstream fitting
  4. Watch for bubbles forming. Any bubble, however small, is a leak. Tighten or swap the fitting.

Never use a flame to check for leaks. Never put your ear or eye close to a suspected leak.

Specific hazards by gas

Oxygen — enriches fire. Never use with oil, grease, or hydrocarbon contamination on any part of the system. A reaction that would normally smoulder becomes an explosion in oxygen-rich air.

Acetylene — unstable above 200 kPa free pressure. Transport and store upright; a laid-down cylinder allows acetone (the solvent in the cylinder) to migrate to the valve.

LPG — heavier than air. Leaks pool at floor level. Ventilate any enclosed storage area.

CO₂ — asphyxiation risk in confined spaces. Cellars with CO₂ should have alarms and floor-level ventilation.

Nitrogen — inert but can displace oxygen. Large leaks in enclosed spaces cause suffocation without warning.

Hydrogen / helium — lighter than air, collect at ceiling. Ventilation matters.

On-site storage

Compliant storage outside of this guide’s scope in detail, but the basics:

  • Upright, restrained, ventilated.
  • Segregate oxidisers (oxygen) at least 3m from fuels (acetylene, LPG, hydrogen) or use a non-combustible partition.
  • Keep cylinders away from heat sources and direct sunlight.
  • No combustibles (cardboard, pallets, oily rags) within 3m.
  • Label full vs empty and store separately.
  • Lock the storage area if not constantly supervised.

When to call Puregas

  • Cylinder fails inspection — we’ll swap it on the next run.
  • Valve seized or leaking from the cylinder itself — don’t attempt to fix.
  • Suspected contamination — we’ll quarantine and investigate at the depot.
  • Near-miss or incident — report it to us as well as WorkSafe. We learn from incidents too.

Training and team habits

Every person who connects or moves cylinders on your site should know the inspection checklist. The single biggest predictor of cylinder incidents in trade settings is a quick connection by someone who hadn’t been trained on the basics. Five minutes of training per person pays for itself the first time they catch a bad cylinder.

Print the checklist above, laminate it, hang it next to the cylinder storage. We supply a printable version on request.

Incident recording — simple, useful

Log any rejected cylinder, damaged valve, or near-miss. A one-line entry per incident is enough. Over a year you’ll see patterns — always the same driver, always a specific gas, always after long transport. That’s data you can act on.

We keep our own incident log at the depot for the cylinders we fill. If one of our cylinders fails on your site, let us know — we’ll investigate and adjust our fill process if needed.

Order from us

Related

Gas

Industrial Oxygen

Industrial oxygen for oxy-fuel cutting, brazing, heating and metal fabrication.

Gas

Acetylene

Acetylene fuel gas for oxy-fuel cutting, welding, brazing and heating.

Gas

Nitrogen — Food Grade

Food-grade nitrogen for dispense, preservation, MAP and food-processing applications.

Gas

Argon

Straight argon for TIG welding, aluminium work, purging and plasma-assist jobs.

Gas

LPG — Home & Fixed-Site

Home and fixed-site LPG for hot water, heating, cooking and standard residential or small-business setups.

Gas supply. No runaround.

Tell us what you need. We’ll confirm timing, paperwork and the next step.
Most metro orders placed by 2pm arrive next business day. Other zones run on schedule.
Puregas Australia Gas Supplier
Gas supply. Done right.
Australian-owned gas supply for industrial, welding, hospitality, food-grade, LPG and specialist supply needs.

Clear terms. Straight pricing. Specialist gas advice. One number.
Welding, hospitality and selected cylinder gases available nationally through 200+ dealer locations. Specialist supply confirmed by location.
One number · Orders · Trade accounts · Technical & SDS · Wholesale.
Melbourne operations
Victoria, Australia
Mon–Fri 8–4:30
© 2026 Puregas Pty Ltd. All rights reserved.